This is the exact control of a typical waste fuel boiler, nothing other than conveyor control is necessary. Steam pressure is controlled by the conveyor speed. Unless someone is standing on the conveyor with a fire hose, the moisture content should vary day to day, but not minute-to-minute. What you may find is that is is difficult to control the flame at ...


1

IMHO, you don't really need AI. PID (or even PI) would be sufficient in this problem. Arguably, you might need to add a cascade controllers (or two), but it should be sufficient. Although AI is powerful, it still needs a lot of tailoring (probably training of the model), and at the end of the day you end up with a black box that could be difficult to debug.